Inverter Specifications
| SKU | VIC-MultiPlus-II-12/3000/120-50-120V-UL |
|---|---|
| Operating type | Off-grid |
| Inverter function | Inverter/charger |
| Continuous AC output power (W) | 2400.0 |
| AC output rating conditions | 2400 W at 25°C; 2200 W at 40°C; 1700 W at 65°C. Transfer time <20 ms. |
| Continuous apparent power (VA) | 3000.0 |
| AC output voltage (V) | 120 |
| AC output frequency (Hz) | 60 |
Show all specifications (45)Show fewer specifications
| AC phase configuration | Single-phase |
|---|---|
| Output waveform | Pure sine wave |
| Battery support | Required |
| Nominal battery voltage (V) | 12 |
| Min battery voltage (V) | 9.5 |
| Max battery voltage (V) | 17.0 |
| Outage backup capability | Yes |
| Backup/EPS output power (W) | 2400.0 |
| Backup output voltage (V) | 120 |
| Surge output power (W) | 5500.0 |
| Max AC battery charging current (A) | 120.0 |
| Generator input supported | Yes |
| AC input voltage (V) | 120 |
| AC input frequency (Hz) | 55–65 |
| Max AC input current (A) | 50.0 |
| AC pass-through current (A) | 50.0 |
| Peak efficiency (%) | 93.0 |
| Idle/no-load consumption (W) | 13.0 |
| Standby consumption (W) | 3.0 |
| Efficiency and consumption conditions | Standby consumption is Search mode. |
| Parallel operation supported | Yes |
| Max parallel units | 6 |
| Parallel phase configurations | Single-phase, Split-phase, Three-phase |
| Communication interfaces | VE.Bus |
| Monitoring app or portal | Victron VRM |
| Remote control functions | Remote monitoring, Remote settings, Remote on/off |
| Required monitoring accessories | Cerbo GX or another compatible GX device and internet connection |
| Monitoring subscription requirements | VRM portal is free of charge. |
| Length (mm) | 148.0 |
| Width (mm) | 277.0 |
| Height (mm) | 578.0 |
| Weight (kg) | 19.0 |
| Enclosure rating | IP22 |
| Min operating temperature (°C) | -40.0 |
| Max operating temperature (°C) | 60.0 |
| Temperature and altitude derating | 2200 W at 40°C and 1700 W at 65°C. |
| Cooling method | Fan-cooled |
Description
SKU Mfg: VIC-MultiPlus-II-12/3000/120-50-120V-UL
SKU: PMP122305122
DESCRIPTION
The MultiPlus-II combines the functions of the MultiPlus and the MultiGrid.
It has all the features of the MultiPlus, plus an external current transformer option to implement PowerControl and PowerAssist and to optimize self-consumption with external current sensing (max. 32A).
It also has all the features of the MultiGrid with built-in anti-islanding and an increasingly long list of country approvals.
PowerAssist
The MultiPlus-II will prevent overload of a limited AC source, such as a generator or shore power connection. First, battery charging will automatically be reduced when otherwise an overload would occur. The second level will boost the output of a generator or shore side supply with power taken from the battery.
Uninterrupted AC power (UPS function)
In the event of a grid failure, or when shore or generator power is disconnected, the inverter within the Multi is automatically activated and takes over the supply to the connected loads. This happens so fast (less than 20 milliseconds) that computers and other electronic equipment will continue to operate without disruption.
Remote Monitoring and Control
When coupled with a GX device (e.g. Cerbo GX) you can monitor and control your Multi and system or systems' locally (LAN) or remotely via the internet from anywhere in the world, using the free VRM app and free VRM portal website. Access can be from a phone, tablet, laptop or PC for multiple operating systems. There is no end to the level of control, from adjusting your Multi to auto starting a backup generator and more…"
UL listed